Thermocouple Cables

Single pair/multipair Overall Screen with Armor

os armor

Application
These cables are used in thermocouple circuits, petrochemical plants, utilities and industrial
plants.
Specification
Conductor: Solid
Type applicable: KX, EX, JX, TX, NX, KCA, KCB, RCA, RCB, SCA, RCB, BC
Insulation: PVC, PE, XLPE or LSZH thermoplastic material
Wrapping: At least 1 layer of plastic tape
Overall screen: 24 μm aluminium / PETP tape over 7-stranded tinned copper drain wire, 0.5
mm²
Bedding: PE, PVC or LSZH thermoplastic material
Armor: Galvanized round steel wires
Outer sheath: PVC or LSZH thermoplastic material
Color code: According to IEC 60584-3
Flame retardancy: IEC 60332-1
Flame propagation: IEC 60332 cat. C
Temperature range: -30°C up to 70°C during operation. -5°C up to 50°C during installation.

0.5 mm²

Conductor Size

No. of Pairs

Insulation Thickness (mm)

Bedding Thickness (mm)

Diameter of Armor Wire (mm)

Outer Sheath Thickness (mm)

Nominal O.D. (mm)

Weight* (kg/km)

0.5

1

0.4

0.8

0.9

1.3

9.6

206

0.5

2

0.4

0.8

0.9

1.4

12.1

295

0.5

4

0.4

0.9

0.9

1.4

13.4

374

0.5

6

0.4

1.1

0.9

1.4

15.4

480

0.5

8

0.4

1.1

0.9

1.5

16.3

546

0.5

10

0.4

1.2

0.9

1.5

17.9

656

0.5

12

0.4

1.2

0.9

1.5

18.5

703

0.5

16

0.4

1.2

1.25

1.6

21.1

975

0.5

20

0.4

1.2

1.25

1.6

22.5

1093

0.5

24

0.4

1.3

1.25

1.7

24.3

1285

0.8 mm²

Conductor Size

No. of Pairs

Insulation Thickness (mm)

Bedding Thickness (mm)

Diameter of Armor Wire (mm)

Outer Sheath Thickness (mm)

Nominal O.D. (mm)

Weight* (kg/km)

0.8

1

0.4

0.8

0.9

1.3

10.0

227

0.8

2

0.4

0.9

0.9

1.4

13.0

343

0.8

4

0.4

0.9

0.9

1.4

14.3

431

0.8

6

0.4

1.1

0.9

1.5

16.7

567

0.8

8

0.4

1.2

0.9

1.5

17.6

657

0.8

10

0.4

1.2

0.9

1.6

19.4

788

0.8

12

0.4

1.2

1.25

1.6

20.8

999

0.8

16

0.4

1.2

1.25

1.7

22.9

1175

0.8

20

0.4

1.3

1.25

1.7

24.8

1347

0.8

24

0.4

1.3

1.25

1.7

26.3

1556

1.0 mm²

Conductor Size

No. of Pairs

Insulation Thickness (mm)

Bedding Thickness (mm)

Diameter of Armor Wire (mm)

Outer Sheath Thickness (mm)

Nominal O.D. (mm)

Weight* (kg/km)

1.0

1

0.4

0.8

0.9

1.3

10.3

240

1.0

2

0.4

0.9

0.9

1.4

13.4

366

1.0

4

0.4

1.1

0.9

1.4

15.1

489

1.0

6

0.4

1.2

0.9

1.5

17.4

629

1.0

8

0.4

1.2

0.9

1.5

18.2

720

1.0

10

0.4

1.2

1.25

1.6

20.9

1016

1.0

12

0.4

1.2

1.25

1.6

21.5

1094

1.0

16

0.4

1.3

1.25

1.7

24.0

1312

1.0

20

0.4

1.3

1.25

1.7

25.7

1490

1.0

24

0.4

1.3

1.25

1.7

27.3

1727

1.3 mm²

Conductor Size

No. of Pairs

Insulation Thickness (mm)

Bedding Thickness (mm)

Diameter of Armor Wire (mm)

Outer Sheath Thickness (mm)

Nominal O.D. (mm)

Weight* (kg/km)

1.3

1

0.4

0.8

0.9

1.3

10.6

258

1.3

2

0.4

0.9

0.9

1.4

14.6

399

1.3

4

0.4

1.1

0.9

1.5

16.8

546

1.3

6

0.4

1.2

0.9

1.5

19.3

701

1.3

8

0.4

1.2

0.9

1.6

20.4

817

1.3

10

0.4

1.2

1.25

1.6

23.2

1136

1.3

12

0.4

1.2

1.25

1.7

24.2

1240

1.3

16

0.4

1.3

1.25

1.7

26.8

1484

1.3

20

0.4

1.3

1.25

1.7

28.9

1697

1.3

24

0.4

1.5

1.25

1.8

31.5

2025

1.5 mm²

Conductor Size

No. of Pairs

Insulation Thickness (mm)

Bedding Thickness (mm)

Diameter of Armor Wire (mm)

Outer Sheath Thickness (mm)

Nominal O.D. (mm)

Weight* (kg/km)

1.5

1

0.5

0.8

0.9

1.3

11.2

284

1.5

2

0.5

1.1

0.9

1.4

16.1

467

1.5

4

0.5

1.2

0.9

1.5

18.3

627

1.5

6

0.5

1.2

0.9

1.6

21.2

802

1.5

8

0.5

1.2

1.25

1.6

22.9

1082

1.5

10

0.5

1.3

1.25

1.7

25.7

1319

1.5

12

0.5

1.3

1.25

1.7

26.6

1430

1.5

16

0.5

1.3

1.25

1.7

29.3

1697

1.5

20

0.5

1.5

1.25

1.8

32.4

2000

1.5

24

0.5

1.5

1.6

1.9

35.5

2598

*The number here is just approx. weight. It changes according to the insulation material and the conductor used in different type of extension cable and compensating cable.